Rheostatic Braking
14-2 | MW500
14
U
d
rated
DC link voltage (U
d
)(P0004)
F0022 - Overvoltage
Rheostatic
braking actuation
Time
Time
U
d
U
d
P0153
Braking resistor
voltage (BR)
Figure 14.1: Rheostatic braking actuation curve
Steps to enable the rheostatic braking:
With the inverter powered down, connect the braking resistor (refer to the user’s manual, section 3.2 Electrical
Installation).
Setting P0151 for the maximum value: 410 V (P0296 = 0), 810 V (P0296 = 1) or 1200 V (P0296 = 3), according
to the situation, in order to prevent the actuation of the DC link voltage regulation before the rheostatic braking.
DANGER!
Be sure the inverter is OFF and disconnected before handling the electric connections and read
carefully the installation instructions of the user's manual.
DANGER!
Vérifier que le variateur est hors tension et débranché avant de manipuler les connexions électriques
et lire attentivement les instructions d'installation dans le mode d'emploi.