Frequency InverterMW500Motors | Automation | Energy | Transmission & Distribution | CoatingsUser's Manual
4 | MW500General Information- English -The main components of the MW500 are shown in the block diagram of figure 2.1.Analog Input(AI1) (*)Digital Inpu
MW500 | 5 General Information- English -2.3 NOMENCLATURETable 2.1: Nomenclature of the MW500 drivesPr o d u c t and SeriesIdentification of the Model
6 | MW500General Information- English -2.4 IDENTIFICATION LABELSThere are two identification labels: one complete nameplate, located on the side of th
MW500 | 7 General Information- English -2.5 RECEIVING AND STORAGEThe MW500 is supplied packed in a cardboard box. On this package, there is an identif
8 | MW500Installation and Connection- English -3 INSTALLATION AND CONNECTION3.1 MECHANICAL INSTALLATION3.1.1 Environmental ConditionsAvoid: Direct
MW500 | 9 Installation and Connection- English -3.2 ELECTRICAL INSTALLATIONDANGER! The following information is merely a guide for proper installati
10 | MW500Installation and Connection- English -3.2.3 Power ConnectionsShieldWEG industrial motorU/T1U/T1V/T2V/T2W/T3W/T3R/L1 S/L2T/L3R/L1S/L2T/L3Fuse
MW500 | 11 Installation and Connection- English -Power supply capacity The MW500 is suitable for use in a circuit capable of delivering not more th
12 | MW500Installation and Connection- English -Ieffective = Imax . tbr (min) √ 5Where: tbr corresponds to the sum of the b
MW500 | 13 Installation and Connection- English -3.2.3.4 Output ConnectionsATTENTION! The drive has an electronic motor overload protection that mus
14 | MW500Installation and Connection- English -Figure 3.3: Details of the connection of the motor cable3.2.4 Grounding ConnectionsDANGER! The drive
MW500 | 15 Installation and Connection- English -AI1AO1GND+10 VDO2-TRGNDRS485 - B>300 Ω+24 VD O1- R L- N AD O1- R L- CDO1-RL-NFDI1DI2DI3DI4RS485 -
16 | MW500Installation and Connection- English -Table 3.1: Configuration of the switches to select the type of analog input and output signal on the C
MW500 | 17 Installation and Connection- English -3.2.7 Cable Separation DistanceProvide separation between the control and power cables and between th
18 | MW500Installation and Connection- English -3.3.2 Emission and Immunity LevelsTable 3.3: Emission and immunity levelsEMC Phenomenon Basic Standard
MW500 | 19 Keypad (HMIR) and Basic Programming - English -4 KEYPAD (HMIR) AND BASIC PROGRAMMING 4.1 USE OF THE HMIR TO OPERATE THE DRIVEThrough the HM
20 | MW500Keypad (HMIR) and Basic Programming - English -4.2 INDICATIONS ON THE HMIR DISPLAYInverter statusSecondary indicationMeasurement unit(it ref
MW500 | 21 Keypad (HMIR) and Basic Programming - English -4.3 OPERATING MODES OF THE HMIR The HMIR must be configured via hardware on S10 DIP-switch b
22 | MW500Keypad (HMIR) and Basic Programming - English -Figure 4.3 illustrates the basic browsing of the operating modes of the HMIR. Monitoring Mode
MW500 | 23 Keypad (HMIR) and Basic Programming - English -NOTE!When the drive is in the fault state, the main display indicates the number of the faul
User’s ManualSeries: MW500Language: EnglishDocument Nº: 10002218015 / 01Publishing Date: 02/2015
24 | MW500Keypad (HMIR) and Basic Programming - English -
MW500 | 25 Powering up and Start-up- English -5 POWERING UP AND START-UP5.1 PREPARATION AND POWERING UPThe drive must be installed according the chapt
26 | MW500Powering up and Start-up- English -5.2 CONSIDERATIONS FOR INTEGRATED MOUNTING IN VENTILATED MOTORS In order to keep the temperature rise o
MW500 | 27 Powering up and Start-up- English -5.3 START-UP 5.3.1 Start-up (using Superdrive and default circuit configuration)When there is no possibl
28 | MW500Powering up and Start-up- English -5.3.2 STARTUP Menu (Using Remote Keypad (HMIR)) The start-up is explained in a very simple way, using the
MW500 | 29 Powering up and Start-up- English -5.3.2.2 VV W Control Type (P0202 = 5)Seq Indication on the Display / Action Seq Indication on the Displa
30 | MW500Powering up and Start-up- English -Seq Indication on the Display / Action Seq Indication on the Display / Action11 16 If necessary, modify
MW500 | 31 Powering up and Start-up- English -5.3.3 Menu BASIC – Basic ApplicationSeq Indication on the Display / Action Seq Indication on the Display
32 | MW500Troubleshooting and Maintenance- English -6 TROUBLESHOOTING AND MAINTENANCE6.1 FAULT AND ALARMSNOTE!Refer to the quick reference and to the
MW500 | 33 Troubleshooting and Maintenance- English -6.3 DATA TO CONTACT THE TECHNICAL ASSISTANCEFor information or service request, it is important t
Summary of ReviewsThe information below describes the reviews made in this manual.Review Description Chapter00 First edition -01 General review and in
34 | MW500Troubleshooting and Maintenance- English -Table 6.3: Periodic inspection every 6 monthsComponent Abnormality Corrective ActionTerminals, con
MW500 | 35 Optional Kits and Accessories - English -7 OPTIONAL KITS AND ACCESSORIES 7.1 OPTIONAL KITS The optional kits are hardware resources added
36 | MW500Optional Kits and Accessories - English -Table 7.1: Accessory modelsWEG Item Name DescriptionControl Accessories (refer to table 7.2 for a
MW500 | 37 Technical Specifications - English -8 TECHNICAL SPECIFICATIONS 8.1 POWER DATA Power Supply: Tolerance: -15 % to +10 %. Frequency: 50/6
38 | MW500Technical Specifications - English -OUTPUTS(*)REL AY 1 relay with NC/NO contact. Maximum voltage: 240 Vac. Maximum current: 0.5 A.
MW500 | 39 Technical Specifications - English -Table 8.2 (cont.): Codes and standardsELECTROMAGNETICCOMPATIBILITY (EMC)STANDARDS EN 61800-3 - Adjust
40 | MW500Appendix AAppendix AAPPENDIX A – PARTSFrontal coverFront cover screwsMotor connectionbox screwsMain caseMotor connection boxWall adapter pla
MW500 | 41 Appendix AAppendix AFrame A432195106781 - XE1 grounding connection screw2 - Intermediate connection box screw 3 - LED indicators 4 - Motor
42 | MW500Appendix AAppendix AFrame B12345116789101 - XE1 grounding connection screw 2 - Intermediate connection box screw 3 - LED indicators 4 - Brak
MW500 | 43 Appendix BAppendix BKnob ReferenceAuxiliary inputsXC10 (remote keypad (HMIR)) inputComplete drive nameplateGrounding pointsInput power conn
Index 1 SAFETY INSTRUCTIONS ... 11.1 SAFETY WARNINGS IN THIS MANUAL ...
44 | MW500Appendix BAppendix BAPPENDIX B – TECHNICAL SPECIFICATIONSTable B .1: List of models of MW500 series, main electrical specifications Inverter
MW500 | 45 Appendix BAppendix BTable B.2: Input and output currents, overload currents, carrier frequency, surrounding air temperature and power losse
46 | MW500Appendix BAppendix BFrame A161,56,362409,45177,66,9996,63,8171,86,761254,92622,44973,82953,74562,2x 56 [2,2]153,76,05101,84,011204,72151,85,
Appendix CAppendix CMW500 | 47 Frame B206 ( 8.1)18 9 ( 7.46 )269 (10.61)102 (4.03)56 x 56(2.20 x 2.20)114 (4.5)113 (4.45)18 8 ( 7. 3 9 )141 (5.55)78
Appendix C Appendix C48 | MW500APPENDIX C – MOUNTING INSTRUCTIONSIntegrate Mounting InstructionsStep Action Step Action1 3 Install the motor wires u
Appendix CAppendix CMW500 | 49 Wall Mounting InstructionsStep Action Step Action1 3 For wall mounting, use the adaptation plate accessory. Use a
Index5 POWERING UP AND START-UP ...255.1 PREPARATION AND POWERING UP ...
MW500 | 1 Safety Instructions- English -1 SAFETY INSTRUCTIONSThis manual contains the information necessary for the correct use of the MW500 drive.It
2 | MW500Safety Instructions- English -1.3 PRELIMINARY RECOMMENDATIONSDANGER!Always disconnect the general power supply before changing any electricco
MW500 | 3 General Information- English -2 GENERAL INFORMATION2.1 ABOUT THE MANUAL This manual contains information for the proper installation and ope