Quick Reference of Parameters, Alarms and Faults
English
MW500 | 27
Fault / Alarm Description Possible Causes
F0239
Profibus DP
Interface Offline
It indicates interruption in
the communication between
the Profibus DP network and
the inverter. The Profibus DP
communication interface went into
offline status.
Check if the network master is correctly configured
and operating properly.
Check for short circuit or poor contact on the
communication cables.
Check if the cables are not misconnected or inverted.
Check if the termination resistors with the right value
were installed only at the end of the main bus.
Check the network installation in general – cabling,
grounding.
F0240
Profibus DP
Module Access
Fault
It indicates fault in the access to
the Profibus DP communication
module data.
Check if the Profibus DP module is correctly fitted.
Hardware errors due to improper handling or
installation of the accessory, for instance, may cause
this fault. If possible, carry out tests by replacing the
communication accessory.
F0700
Remote HMI
Communication
Fault
No communication with remote
HMI, but there is no speed
command or reference for this
source.
Check if the communication interface with the HMI is
properly configured in parameter P0312.
HMI cable disconnected.
F0710
SoftPLC Oversize
The SoftPLC user program size
exceeds internal memory space.
The user application logic is too large, more than 8 kB.
F0711
SoftPLC Program
Failure
There is some failure in the
SoftPLC user program.
The SoftPLC user program is corrupted.
There was a timeout in the SoftPLC scan.
TABLE OF SITUATIONS THE STATUS CONFIG
The CONFIG status is indicated by the HMI “CONF” status, as well as in parameters P0006 and P0680. Such status
indicates that the MW500 cannot enable the output PWM pulses because the inverter configuration is incorrect or
incomplete.
The table below shows the situations of CONFIG status, where the user can identify the origin condition through
parameter P0047.